OPTIUPS(8) NUT Manual OPTIUPS(8)
NAME
optiups - Driver for Opti-UPS (Viewsonic) UPS and Zinto D (ONLINE-USV)
equipment
NOTE
This man page only documents the hardware-specific features of the
optiups driver. For information about the core driver, see
nutupsdrv(8).
SUPPORTED HARDWARE
optiups was originally written against a PowerES 280es in nut-0.45. It
was revised for nut-2.0.1 and tested against a PowerES 420E. It is
expected to work with at least the PowerES, PowerPS, and PowerVS
models.
This driver additionally supports a Zinto D from ONLINE USV-Systeme AG
because of their very similar commands, but it is unknown if it also
works with other UPS from them.
This driver will not work with the PowerES stock serial cable. You will
need to construct your own three conductor cable:
UPS 6 -> PC 3
UPS 9 -> PC 2
UPS 4 -> PC 5
The cable for Online-USV uses pin UPS 7 (not UPS 4) -> PC 5.
EXTRA ARGUMENTS
This driver supports the following optional settings in the ups.conf(5)
file:
status_only
Only poll for critical status information. Without this, optiups
(and all NUT drivers) poll all sorts of information from the UPS
fairly often. It is probably not often enough to hurt anything, so
this option probably is not very useful, unless you have a flaky
serial connection or a highly loaded machine.
nowarn_noimp
Does not print warnings when the UPS reports that a variable is not
implemented or not pollable. Without the option you will get a
message sent to your system logs each time NUT polls the UPS. If
you specify nowarn_noimp, this message will only be logged once.
fake_lowbatt
This forces the low battery flag true. Without it, if you want to
test your UPS, you will have to unplug it and wait until the
battery drops to a low/critical voltage level before NUT will
respond and power down your system. With the flag, NUT should power
down the system soon after you pull the plug. When you are done
testing, you should remove this flag.
For basic shutdown configuration testing, the command upsmon -c fsd
is preferred.
powerup
Zinto D from ONLINE-USV cannot be identified when switched to
standby. Set this flag to allow the driver to power-up your Zinto
UPS. This will also power-up your equipment connected to the UPS!
BUGS
On the 420E, ups.serial and ups.temperature are unsupported features.
This is not a bug in NUT or the NUT driver, just the way things are
with this UPS.
AUTHOR
Russell Kroll, Scott Heavner, Matthias Goebl
SEE ALSO
The core driver:
nutupsdrv(8)
Internet resources:
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
Network UPS Tools 2.7.3 04/17/2015 OPTIUPS(8)