EDS00xx(3) One-Wire File System EDS00xx(3)
NAME
EDS - Embedded Data Systems Sensors
EDS0064
- Temperature
EDS0065
- Temperature and Humidity
EDS0066
- Temperature and Barometric Pressure
EDS0067
- Temperature and Light
EDS0068
- Temperature, Barometric Pressure and Light
EDS0070
- Vibration
EDS0071
- RTD 4-wire temperature
EDS0072
- RTD 3-wire temperature
EDS0080
- 8 Channel Analog Current Input
EDS0082
- 8 Channel Analog Voltage Input
EDS0083
- 4 Channel Analog Current Input
EDS0085
- 4 Channel Analog Voltage Input
EDS0090
- 8 Discrete I/O
SYNOPSIS
Embedded Data Systems microprocessor-based sensors
Sub-type ( all )
7E [.]XXXXXXXXXXXX[XX][/[ device_id | device_type | tag ]]
Memory ( all )
7E [.]XXXXXXXXXXXX[XX][/[ memory | pages/page.[0-2|ALL] ]]
Standard ( all )
7E [.]XXXXXXXXXXXX[XX][/[
See the file man3/standard_mini.3so.
]]
Temperature ( EDS0064/5/6/7/8 )
7E.XXXXXXXXXXXX/EDS006X [/[ temperature | counters/seconds |
alarm/temp_[hi|low] | alarm/clear | set_alarm/temp_[hi|low] |
threshold/temp_[hi|low] ]]
Humidity ( EDS0065/8 )
7E.XXXXXXXXXXXX/EDS006X [/[ humidity | humidex | dew_point | heat_index
| alarm/humidity_[hi|low] | alarm/humidex_[hi|low] |
alarm/dew_point_[hi|low] | alarm/heat_index_[hi|low] | alarm/clear |
set_alarm/humidity_[hi|low] | set_alarm/humidex_[hi|low] |
set_alarm/dew_point_[hi|low] | set_alarm/heat_index_[hi|low] |
threshold/humidity_[hi|low] |
threshold/humidex_[hi|low] | threshold/dew_point_[hi|low] |
threshold/heat_index_[hi|low] ]]
Barometric Pressure ( EDS0066/8 )
7E.XXXXXXXXXXXX/EDS006X [/[ pressure | inHg | alarm/pressure_[hi|low] |
alarm/inHg_[hi|low] | alarm/clear | set_alarm/pressure_[hi|low] |
set_alarm/inHg_[hi|low] | threshold/pressure_[hi|low] |
threshold/inHg_[hi|low] ]]
Light ( EDS0067/8 )
7E.XXXXXXXXXXXX/EDS006X [/[ light | alarm/light_[hi|low] | alarm/clear
| set_alarm/light_[hi|low] | threshold/light_[hi|low] ]]
Vibration ( EDS0070 )
7E.XXXXXXXXXXXX/EDS0070 [/[ vib_level | vib_peak | vib_min | vib_max |
counter/seconds | alarm/vib_[hi|low] | alarm/clear |
set_alarm/vib_[hi|low] | threshold/vib_[hi|low] ]]
RTD Temperature ( EDS0071/2 )
7E.XXXXXXXXXXXX/EDS007X [/[ temperature | resistance | raw | delay |
user_byte | calibration/[key|constant] | counter/[seconds|samples] |
alarm/temp_[hi|low] | alarm/RTD_[hi_low] | alarm/clear |
set_alarm/temp_[hi|low] | set_alarm/RTD_[hi_low] |
threshold/temp_[hi|low] | threshold/RTD_[hi_low] ]]
Analog Current ( EDS0080 [0-7] EDS0083 [0-3] )
7E.XXXXXXXXXXXX/EDS0080 [/[ current.[0-7|ALL] | max_current.[0-7|ALL] |
min_current.[0-7|ALL] | threshold/current_hi.[0-7|ALL] |
threshold/current_low.[0-7|ALL] | alarm/current_hi.[0-7|ALL|BYTE] |
alarm/current_low.[0-7|ALL|BYTE] | set_alarm/current_hi.[0-7|ALL|BYTE]
| set_alarm/current_low.[0-7|ALL|BYTE] | counter/seconds | memory |
pages/page.[0-4|ALL]
Analog Voltage ( EDS0082 [0-7] EDS0085 [0-3] )
7E.XXXXXXXXXXXX/EDS0082 [/[ volts.[0-7|ALL] | max_volts.[0-7|ALL] |
min_volts.[0-7|ALL] | threshold/volts_hi.[0-7|ALL] |
threshold/volts_low.[0-7|ALL] | alarm/volts_hi.[0-7|ALL|BYTE] |
alarm/volts_low.[0-7|ALL|BYTE] | set_alarm/volts_hi.[0-7|ALL|BYTE] |
set_alarm/volts_low.[0-7|ALL|BYTE] | counter/seconds | memory |
pages/page.[0-4|ALL]
I/O ( EDS0090 )
7E.XXXXXXXXXXXX/EDS009X [/[ input.[0-7|ALL] | counter/[seconds |
pulses.[0-7|ALL]|reset.[0-7|ALL|BYTE]] |
output/[set.[0-7|ALL|BYTE]|off.[0-7|ALL|BYTE]|reset.[0-7|ALL|BYTE]] |
latch/[state.[0-7|ALL|BYTE]|reset.[0-7|ALL|BYTE]] |
alarm/[hi.[0-7|ALL]|low.[0-7|ALL]|clear] |
set_alarm/[hi.[0-7|ALL]|low.[0-7|ALL]]
LED ( all )
7E.XXXXXXXXXXXX/EDS00XX/LED/[state|control]
relay ( all )
7E.XXXXXXXXXXXX/EDS00XX/relay/[state|control]
FAMILY CODE
7E
TEMPERATURE
EDS006X/temperature
read-only, floating-point
Temperature for the EDS006X series of chips. In the -55C to 125C range,
with 0.0636C precision. The temperature is read every second,
continually. Data is presented in the specified temperature scale,
Celsius by default.
EDS007X/temperature
read-only, floating-point
Temperature for the EDS007X series of chips. Read using a wide-range
precise RTD sensor. Typical range is -60C to 260C with 0.15C accuracy,
although a range of -200C to 850C is possible. The temperature is read
every second unless a longer EDS007X/delay is given. Data is presented
in the specified temperature scale, Celsius by default.
EDS007X/resistance
read-only, floating-point
Actual measured resistance (Ohms) of the RTD element. Useful if the RTD
element doesn't conform to the typical European IEC 60751 standard.
HUMIDITY
EDS006X/humidity
read-only, floating-point
Relative humidity in the 0-100 range (percent). Read every 0.2 seconds.
EDS006X/dew_point
read-only, floating-point
Dew point computed from EDS006X/temperature and EDS006X/humidity
computered every 0.2 seconds. Data is a calculated temperature and is
reported in the specified temperature scale. Default Celsius.
EDS006X/heat_index
read-only, floating-point
Heat index computed from EDS006X/temperature and EDS006X/humidity
computered every 0.2 seconds. Data is a calculated temperature and is
reported in the specified temperature scale. Default Celsius.
EDS006X/humidex
read-only, floating-point
Humidex (popular in Canada) computed from EDS006X/temperature and
EDS006X/humidity computed every 0.2 seconds. Data is a percent and
reported in the 0-100 range.
LIGHT
EDS006X/light
read-only, unsigned integer
Ambient light in Lux. Measured every 0.2 seconds.
PRESSURE
EDS006X/pressure
read-only, floating-point
Ambient pressure, measured every 0.2 seconds. Data in the selected
pressure scale (default mBar).
EDS006X/inHg
read-only, floating-point
Ambient pressure, measured every 0.2 seconds. Data in the inHg scale.
VIBRATION
EDS0070/vib_level
read_only, unsigned integer
Vibration registered by sensor (instantaneous value) in 0-1023 range.
EDS0070/vib_peak
read_only, unsigned integer
Vibration registered by sensor (highest recent value -- slowly decays)
in 0-1023 range.
EDS0070/vib_min
read_only, unsigned integer
Vibration registered by sensor (lowest value) in 0-1023 range.
EDS0070/vib_max
read_only, unsigned integer
Vibration registered by sensor (highest value) in 0-1023 range.
CURRENT
The EDS0080 and EDS0083 measure current in the 4-20mA range, with upper
and threshold limits and the ability to set an alarm and independently
trigger a relay if the value is out of range.
EDS0080/current.[0-7|ALL] EDS0083/current.[0-3|ALL]
read-only, floating point
Current current level. (4-20mA)
EDS0080/max_current.[0-7|ALL] EDS0080/max_current.[0-3|ALL]
EDS0083/min_current.[0-7|ALL] EDS0083/min_current.[0-3|ALL]
read-only, floating point
Maximum and minimum current readings since last alarm/clear command.
VOLTAGE
The EDS0082 and EDS0085 measure voltage in the 0-10V range, with upper
and threshold limits and the ability to set an alarm and independently
trigger a relay if the value is out of range.
EDS0082/volts.[0-7|ALL] EDS0085/volts.[0-3|ALL]
read-only, floating point
Current voltage level. (0-10V)
EDS0082/max_volts.[0-7|ALL] EDS0085/max_volts.[0-3|ALL]
EDS0082/min_volts.[0-7|ALL] EDS0085/min_volts.[0-3|ALL]
read-only, floating point
Maximum and minimum voltage readings since last alarm/clear command.
THRESHOLD
High and low range of acceptable sensor readings. Values outside this
range will trigger an alarm if the corresponding EDS00XX/set_alarm flag
is set.
EDS00XX/threshold/temp_hi EDS00XX/threshold/temp_low
read-write, floating-point
Threshold temperatures in the specified temperature scale. Default
Celsius.
EDS006X/threshold/humidity_hi EDS006X/threshold/humidity_low
EDS006X/threshold/dew_point_hi EDS006X/threshold/dew_point_low
EDS006X/threshold/heat_index_hi EDS006X/threshold/heat_index_low
EDS006X/threshold/humidex_hi tEDS006X/threshold/humidex_low
read-write, floating-point
Threshold humidity values. Dew point and Heat index are in the
specified temperature scale. Default Celsius.
EDS006X/threshold/pressure_hi EDS006X/threshold/pressure_low
EDS006X/threshold/inHg_hi EDS006X/threshold/inHg_low
read-write, floating-point
Threshold barometric pressure values. Pressure is the specified
pressure scale. Default mBar.
EDS006X/threshold/light_hi EDS006X/threshold/light_low
read-write, unsigned
Threshold light (lux) values.
EDS0070/threshold/vib_hi EDS0070/threshold/vib_low
read-write, unsigned
Vibration sensor alarm limits in 0-1023 range.
EDS007X/threshold/resistance_hi EDS007X/threshold/resistance_low
read-write, floating-point
Threshold RTD resistance values (Ohm).
EDS0080/threshold/current_hi.[0-7|ALL]
EDS0080/threshold/current_low.[0-7|ALL]
EDS0082/threshold/volts_hi.[0-7|ALL] EDS0082/threshold/volts_low.[0-7|ALL]
EDS0083/threshold/current_hi.[0-3|ALL
EDS0083/threshold/current_low.[0-3|ALL]
EDS0085/threshold/volts_hi.[0-3|ALL] EDS0085/threshold/volts_low.[0-3|ALL|]
read-write, floating-point
Voltage or current threshold limits
SET ALARM
Set conditional alarm to trigger if corresponding flag is set. Also
must set high and low threshold.
EDS00XX/set_alarm/temp_hi EDS00XX/set_alarm/temp_low
EDS006X/set_alarm/humidity_hi EDS006X/set_alarm/humidity_low
EDS006X/set_alarm/dew_point_hi EDS006X/set_alarm/dew_point_low
EDS006X/set_alarm/heat_index_hi EDS006X/set_alarm/heat_index_low
EDS006X/set_alarm/humidex_hi EDS006X/set_alarm/humidex_low
EDS006X/set_alarm/pressure_hi EDS006X/set_alarm/pressure_low
EDS006X/set_alarm/inHg_hi EDS006X/set_alarm/inHg_low
EDS006X/set_alarm/light_hi EDS006X/set_alarm/light_low
EDS0070/set_alarm/vib_hi EDS0070/set_alarm/vib_low
EDS007X/set_alarm/resistance_hi EDS007X/set_alarm/resistance_low
EDS0080/set_alarm/current_hi.[0-7|ALL|BYTE]
EDS0080/set_alarm/current_low.[0-7|ALL|BYTE]
EDS0082/set_alarm/volts_hi.[0-7|ALL|BYTE]
EDS0082/set_alarm/volts_low.[0-7|ALL|BYTE]
EDS0083/set_alarm/current_hi.[0-3|ALL|BYTE]
EDS0083/set_alarm/current_low.[0-3|ALL|BYTE]
EDS0085/set_alarm/volts_hi.[0-3|ALL|BYTE]
EDS0085/set_alarm/volts_low.[0-3|ALL|BYTE]
read-write, yes-no
Flag to set corresponding out-of-range alarm. "1" turns on flag, and
"0" turns off.
ALARM
Show or clear the out-of-range flags. When set, the device will respond
to a conditional search. Clearing the flags is performed with the
EDS00XX/alarm/clear command, not just having the measured value return
to the center range.
EDS00XX/alarm/clear
write-only, yes-no
Write "1" to clear ALL the alarm flags.
EDS00XX/alarm/temp_hi EDS00XX/alarm/temp_low
EDS006X/alarm/humidity_hi EDS006X/alarm/humidity_low
EDS006X/alarm/dew_point_hi EDS006X/alarm/dew_point_low
EDS006X/alarm/heat_index_hi EDS006X/alarm/heat_index_low
EDS006X/alarm/humidex_hi EDS006X/alarm/humidex_low
EDS006X/alarm/pressure_hi EDS006X/alarm/pressure_low
EDS006X/alarm/inHg_hi EDS006X/alarm/inHg_low
EDS006X/alarm/light_hi EDS006X/alarm/light_low
EDS0070/alarm/vib_hi EDS007X/alarm/vib_low
EDS007X/alarm/resistance_hi EDS007X/alarm/resistance_low
EDS0080/alarm/current_hi.[0-7|ALL|BYTE]
EDS0080/alarm/current_low.[0-7|ALL|BYTE]
EDS0082/alarm/volts_hi.[0-7|ALL|BYTE]
EDS0082/alarm/volts_low.[0-7|ALL|BYTE]
EDS0083/alarm/current_hi.[0-3|ALL|BYTE]
EDS0083/alarm/current_low.[0-3|ALL|BYTE]
EDS0085/alarm/volts_hi.[0-3|ALL|BYTE]
EDS0085/alarm/volts_low.[0-3|ALL|BYTE]
EDS0090/alarm/hi[0-7|ALL] EDS0090/alarm/low[0-7|ALL]
read-only, yes-no
Show corresponding out-of-range alarm. "1" means in alarm state. Can
only be turned off with clear
RELAY
Optionally found on the EDS006X and EDS007X. Can be controlled by
software or the alarm condition.
EDS00XX/relay/control
read-write, unsigned
Set the relay control scheme:
0 alarm control with hysteresis
1 alarm control but need EDS00XX/alarm/clear to unset
2 Control with EDS00XX/relay/state
3 Always off
EDS00XX/relay/state
read-write, yes-no
Turn the relay on or off if the EDS00XX/relay/control is set to 2
LED light
Found on the EDS006X and EDS007X. Can be controlled by software or the
alarm condition.
EDS00XX/LED/control
read-write, unsigned
Set the LED control scheme:
0 alarm control with hysteresis
1 alarm control but need EDS00XX/alarm/clear to unset
2 Control with EDS00XX/LED/state
3 Always off
EDS00XX/LED/state
read-write, yes-no
Turn the LED on or off if the EDS00XX/LED/control is set to 2
COUNTER
EDS00XX/counter/seconds
read-only, unsigned integer
Approximate seconds since power up.
EDS0090/counter/pulses.0-7 | ALL
read-only, unsigned integer
Pulses on each channel since power up or reset. Channel should be set
to input ( EDS0090/output/set.x =0 )
EDS0090/counter/reset.0-7 | ALL | BYTE
read-write, yes-no
Clear the pulse count on the corresponding channel.
EDS007X/counter/samples
read-only, unsigned integer
Approximate samples since power up.
MEMORY
memory
read-write, binary
96 bytes of memory. Not all is writable. Access to EDS00XX functions is
better accomplished through the data fields, which expose all the chip
features.
pages/page.0 ... pages/page.2 pages/page.ALL
read-write, binary
Memory is split into 3 pages of 32 bytes each. Only page 2 is writable.
ALL is an aggregate of the pages. Each page is accessed sequentially.
EDS008X/memory
read-write, binary
160 bytes of memory. Not all is writable. Access to EDS008X functions
is better accomplished through the data fields, which expose all the
chip features. The EDS008X has more memory than the other chips, so a
separate entry in the sudbirectory makes it available.
EDS008X/pages/page.0-4 EDS008X/pages/page.ALL
read-write, binary
Memory is split into 5 pages of 32 bytes each. Only page 5 is writable.
The EDS008X has more memory than the other chips, so a separate entry
in the sudbirectory makes the extra pages available. ALL is an
aggregate of the pages. Each page is accessed sequentially.
SUB-TYPE
tag
read-only, ascii
Text description of the device. Up to 30 characters.
device_type
read-only, ascii
Device name. E.g: "EDS0071"
device_id
read-only, unsigned
Number corresponding to the hexidecimal type. E.g:
EDS0071 -> 0x0071 -> 113 in decimal
STANDARD PROPERTIES
See the file man3/standard.3so.
ALARMS
None.
DESCRIPTION
See the file man3/description.3so.
EDS00XX Overview
The EDS00XX sensors are a family of devices from Embedded Data Systems.
Although provisional support for several types is included, only early
EDS0071 has been tested with OWFS.
The sensors all share the same 7E family code. They have the same first
memory page layout with a text tag property that describes them, and a
sub-type field giving the particular sensor. The data properties shown
in a directory listing will be specific to the sensor sub-type.
EDS0071
The EDS0071 (3) is a micro-processor based 1-wire slave made by EDS
(Embedded Data Systams). Is uses a high accuracy and extended range RTD
sensor to accurately measure temperatures.
Memory
The EDS00XX sensors are read and controlled by accessing parts of their
on-chip memory. Although the raw memory contents are exposed in the
memory and pages fields, all the available functionality is best
accessed by the other fields. In fact, directly changing memory will
confuse OWFS.
Relay and LED
All the EDS00XX sensors have an LED and optional relay. Both can be
controlled either directly, or when the sensors reaches an alarm state.
ADDRESSING
See the file man3/addressing.3so.
DATASHEET
EDS0064 EDS0065 EDS0066 EDS0067 EDS0068
https://docs.google.com/viewer?a=v&pid=explorer&chrome=true&srcid=0B_K3iXLLAI7vN2E4NGUwMGItMzc5MS00NDNmLTljZGYtN2NmM2Q3YWE5NmVh&hl=en
EDS0070
http://www.embeddeddatasystems.com/assets/images/supportFiles/manuals/EN-
UserMan%20%20OW-Vibration%20V01.pdf
EDS0071 EDS0072
https://docs.google.com/viewer?a=v&pid=explorer&chrome=true&srcid=0B_K3iXLLAI7vMjVhNWQzYzItZTRhMi00NGY2LWI4NTQtYjZlYTgzYzY0NmNm&hl=en
EDS0080 EDS0083
https://eds.zendesk.com/attachments/token/ulnpj6mvpp6yzwo/?name=EN-
USERMAN+OW-IO-AIX-420+v1p0.pdf
EDS0082 EDS0085
https://eds.zendesk.com/attachments/token/vyai6ylpw6edala/?name=EN-
USERMAN+OW-IO-AIX-10V+v1p0.pdf
EDS0090
8 Discrete I/O
SEE ALSO
See the file man3/seealso.3so.
AVAILABILITY
http://www.owfs.org
AUTHOR
Paul Alfille (paul.alfille@gmail.com)
OWFS Manpage 2003 EDS00xx(3)